Frequently Asked Questions

My pool heat pump trips the circuit when the compressor starts up.

Does your pool heat pump trip your electricity cabinet when it starts up? There are several possibilities:

For a newly installed heat pump:

  • The meter trips: increase the limits of your energy plan with your energy supplier
  • The circuit breaker trips: check that the right circuit breaker is installed and that the correct cable cross-section is used (refer to the heat pump manual).


For an older, previously-installed heat pump:

  • The meter trips: increase the limits of your energy plan with your energy supplier.
  • The circuit breaker trips: check the start-up condenser, it will probably need to be replaced. If this continues after the replacement, check that the correct circuit breaker has been installed and the correct cable cross-section is used (refer to the heat pump manual).
  • The residual current circuit breaker trips: ask for a visit from a refrigeration specialist.
Related questions
Discover all the products: Heat Pumps
See all products